What are the requirements for storage within 18 inches of a sprinkler head?

The 18-inch (0.46-millimeter) dimension is not intended to limit the height of shelving on a wall or shelving against a wall in accordance with 5-6.6. Where shelving is installed on a wall and is not directly below sprinklers, the shelves, including storage thereon, can extend above the level of a plane located 18 inches (0.46 millimeters) below ceiling sprinkler deflectors.

Shelving, and any storage thereon, directly below the sprinklers cannot extend above a plane located 18 inches (0.46 millimeters) below the ceiling sprinkler deflectors.